Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how gen. load increase or decrease ? what happen with gen on that time

Answer Posted / sagar upadhyay

If we connect an equipment that demands a high current
( offers a low resistance), then we call it a large load.
Similarly, equipment having large resistance will be called
as a small load. As the load changes, the load current
supplied by he gen also changes. It depends on the type of
gen. how it behaves in such cases. But generally the voltage
drop will reduce if the load is increased until & unless the
prime mover input to the gen is not increased.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the formula to calculate voltage drop/loss on 66KV Transmission Line?

3699


kindly send me 11KV MV motor differential protection procedure by primary injection method.

1447


What is the ideal position cooling fan inside the dc motor?

2093


What is the main purpose of c.f.b.c.boiler

1722


why high speed tripping relay is used in protection circuit why not normal relay

1491


what are the differences between 'exhaust fan', 'heavy-duty exhaust fan' & 'super heavy duty exhaust fan'. what are their power ratings ?

2086


How is the resonant peak, resonant frequency, and bandwidth determined from nichols chart?

1084


How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?

4473


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2152


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1853


how hazordious area is classified at an oil & gas plant and categorise suitable class of electric equipment in that area like induction motors, LCS, Lighting Fixtures Fluerescent/Flood lights Mercury& sodium lights, J.Bs, Power Cables etc

1848


how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size

2379


how to copy from plc ge fanuc versamax series,all input and output, adress, and printout.

2505


whatare the disadvantages occur,if the form factor of transmission will not be equal to 1.11

1866


how to find the torque of the single phase synchronous motor by doing an experiment

1940