How to increase home power factor? Can we connect capacitor
directly? How to select capacity of capacitor?
Answer Posted / srinivasa rao talasila
There is a formula to calculate capacity of capacitor
required for a certain inductive load in KW
KVAR=KW*(Tan of running PF angle-Tan of desired PF angle)
Per suppose my plant is running 0.84 i need to take it to
0.98 at a load of 800KW
KVAR=800*(Tan 32.86-Tan 11.48)
KVAR=800*(0.6459-0.2030)
KVAR=800*0.4429
=354.32 say 355KVAR
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How to decide CT & PT ratings for a given transmission line carrying some rated voltage?
Is phenomenon of resonance is harmfull fr the machine? if not or if yes please explain it?
What is the numerical quantity of sqcm?
what is the reactive power what is the use of it in system
Where is the best place to mount distribution panel in a house.
explain all the classes with example
What is warm / cold start of HT motors. How many warm start & cold start are possible in a day?
How would your past experience translate into success in this job?
size of condotory fron voltage level
Which of the following alternatives will be cheaper (1) A 100 h.p AC, 3-phase motor (2) Four motors of 25 h.p each (3) Five motors of 20 h.p each (4) 10 motors of 10 h.p each explain
what is differnce btwen lll and lllg faults
Define damping ratio.
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?
12.5 tons a/c is their how much kva generator can recommend to the customer.