i am working in the automation company...i want to just know
how actully pid control valves are tune????...
Answer Posted / sumith
PID control valves works on 4-20 ma ,plc gives 4-20 ma to
pid valve according to the difference between setpoint and
actual value (for e.g s.p temp = 90 degc actual = 30
degc)now plc will give 20ma to pid valve for temp to reach
the setpoint.pid valve should have continous air supply.
to calibrate pid valve there is span and zero adjustment.
pid tuning is done in plc not in valve.pid tuning in plc is
trial and error type tuning.
we have to some values in P and I and D and check whether it
is reaching the setpoint smoothly
| Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
can we copy the software from a transmitter using hht(hart 275) ?
Which is your favourite subject & explain any one topic of it.
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
What is critcal speed. what is resonant frequency. why we want to cross crtcal speed on higher RPM (early).
selection of the zener barrier for the hazardeous area zone 0
defination of radial vibration?
how to turbine speed measurement?
please send data bank of quetions answers on analytical instrumentation.
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
If P will increase then what will happen with PID?
few questions on RS 232,1 question on relationship of impedance and turns ratio, many questions on flowmeters
how can we tune a PID. If it is by zeiger nichols method..please explain briefly with help of an example.
Can anyone convert a 5/2 way or 3/2 way valve into an ISO valve?