Dear all,
Can anybody tell me that how to choose CT for a specific
load? I have a 200kw induction motor, which ratio CT should
be installed? Is there a formula or calculation that
determines the CT ratio for a load?
Regards.
Answer Posted / k.prakashchandra
Another method.Divide KW by 0.75 (lowest pf expected) to get
KVA. Calculate current which is about 380 A at 400 V line
voltage.You can choose a CT 0f either 400 or 500 A as
primary current.The secondary current of CT is decided by
meter and relays.This is generally either 1 or 5 A .
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
advantages and disadvantages of inverse definite minimum time RELAY
What happens if the negative to earth voltage is greater than positive to earth voltage in the battery of substation?
Explain Energy and Power signals?
Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?
what is earthing.how we make it,describe briefly.
How to calculate the copper in HT motors if KW, RPM & Voltage is given
what is different between phase and netural
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
why star point of HT motor not earthed?
The inventer is a battery, but if lost current at home u will turn on the fan but the is AC and inventer battery is dc . Then how the fan was rotating. What device Or machine in fan converst the Dc power to Ac power
132/6.6ππ πππππππππππ πππππππ πππ πππ πππππ πππ πππππππππ. πΈ'ππ πππππππ πππππππππππ ππ 6.6ππ/415π πππ πΈ πππππππ πππππππ ππ ππππ πππππ πππ ππ ππ 13/6.ππ πππππππππππ?? πΈπ π½π.. ππππ π ππ’??
why starting current is high and resistance is almost 0 during the starting of motor dc motor...?
What is the function of a neutral reactor.
If any HVDC line is going with positive & negative(the negative usually have return path of current with earthing electrode). Now the question is if this HVDC earthed electrode which is using as return path and earthed any nearby 400kv or 220kv AC substation equipments. which will be the impact of this on AC substation & its equipment, how severe may be this and what should be the minimum distance require between HVDC earthed electrode and AC substation equipments? It's really an high engineering level question...Dare to answer and increase your knowledge.
what is the IPC ? & what the uses ?