Dear all,
Can anybody tell me that how to choose CT for a specific
load? I have a 200kw induction motor, which ratio CT should
be installed? Is there a formula or calculation that
determines the CT ratio for a load?
Regards.
Answer Posted / k.prakashchandra
Another method.Divide KW by 0.75 (lowest pf expected) to get
KVA. Calculate current which is about 380 A at 400 V line
voltage.You can choose a CT 0f either 400 or 500 A as
primary current.The secondary current of CT is decided by
meter and relays.This is generally either 1 or 5 A .
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
what is transistors comprised of?
what are the values of VRY,VYB,VBR,Vry,Vyb,Vbr,Vrn,Vyn,Vbn for Magenetic balance test of 100 KVA and 63 KVA Distribution transformer
- two pumps must work with them at the same time but if the first pump start the second pump must delayed for some time to start also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it
1.what is meaning of curve into a mcb. 2.what is basic reason changing of curve
What do you understand by external characteristics of a d.c. Generator?
dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour
Is it advantages of having star-delta vfd than normal star vfd , if yes why?
pls tell me about ups internal connection & we have given only 3 phase supply to ups system how get 4 wire (R Y B N )
where is the need for short circuit test for 3 see is required and why? can you explain in brief with application
In dc ckt. 24v or 110v, which one is more efficient and why?
Explain the different regions in frequency response?
sir please send me iocl written test paper in my e-mail account. i'll be obliged to you........ thank u roshan
Dear sir, my knowledge about cable size determination is limited. Though I read examples I could not calculate the Cable size required for electric driven pump 40 KW, 380 Volt, 50 HZ, 50 meter from transformer and it is three phase star delta starting. Please help as there is no one in my surroundings to help.
What is state space method ? Why its used ? Can it applicable on linear, non-linear, 1st order, higher order, homogeneous, non-homogeneous, open-loop , closed loops , stable & unstable systems ?
what is the difference between switchgear and circuit breakers and is there any difference between outdoor and indoor switchgear and circuit breakers , and how would you differentiate between switch yard and substation and grid station . thanks