check list of maintenance of transformer?
Answer Posted / somashekar
) Power Isolation of transformer with proper permit
2) Earthing of all hv/lv terminal after physical isolation.
3) Cleaning of transformer with lint free cotton.
4) Oil leakages checks for all joint
5) Silica gel re heating if reqd.
6) OLTC/OFTC local operation Check(calibration of motor
over load relay)
7) OLTC continuity check(by connecting analog meter across
across all the phase terminal and OLTC operation)
8) Alarm and trip circuit checking of OTI,WTI, MOLG, Mulsy
fire,Buchholtz of main and OLTC
9) BDV of main Oil and OLTC oil
10) PPM of oil
11) Tan delta of bushing, main Oil and OLTC oil
12) Magnetic balence
13) Ratio test in every tap
14) Winding resistance
15) Insulation resistance after LA disconnection
16) Secondary injection test of protection relays with CT &
PT test
17) Cooling Fan testing by OTI/WTI temprature (manully by
rotating the prob)
18) Other inter lock if any
Note: Normaly Annual maintenance cover most of the the
test, mainly 5 year test contain all the checks depends on
manufacture and customer check list.
| Is This Answer Correct ? | 21 Yes | 4 No |
Post New Answer View All Answers
What is bridge rectifier and explain with details
what is kvarh? Please define it With calculation General motors ?
Explain the working principle of Synchronous Generator and Assynchronous generator?
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
what are the differant std sizes of cable trenches?
What is the basic principal, by which DC voltage level is increased more than the supplied AC voltage during conversion. As upto AC level it is contorrled by firing anlge but after maximum level how is it possible.Please clear picture. OR we have to supply the higher level AC?
what is earthing transformer? draw the winding dia.of earthing transformer.
nwhat are the main Components of servo motor?
how to check three phase motor torque value?
what is acceptance test in electrical engineering.
two phases with neutral supply can be taken in 3C X 10 sq.mm cable .
What are the conditions to be satisfied for parallel operation of dc generators?
How do i right a ladder diagram that has 1 actuator that performs a full stroke followed by a half stroke
What conditions are required for transformer to operate at low frequencies ?
Why is remote backup preferred to local backup?