how to do 'pole drop test' on AC generator?

Answer Posted / nizam salih

A pole drop test can be done when the generator is in
standstill condition. Provide a ac voltage of 230V to the
rotor terminals of the salient pole machine and measure the
voltage drop in each pole. At least 5A should flow through
the rotor poles. A small current will not provide good
results. Once the voltage drops are recorded calculate the
drop index as follows.
Index = (max. value - min. value)/avearge value *100 %
An index value of less than 5% reprsents the poles are
good.
This is the usual annual test that we carry out in our
hydro generators.
Nizam Salih, Electrical Engineer, Sri Lanka.

Is This Answer Correct ?    10 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the relationship between voltage,current & frequency?

1262


The ripple frequency in output of fullwave bridge rectifier is a. Half the input b. Twice the input c. Same as input

1808


How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter

6676


Where is the best place to mount  distribution panel in a house.

1625


hi plz send me reliance placement papers..i.e electrical technical papers that have been asked in reliance test.

2462






what is the requirement regarding earthing of Single conductor with AWA

1655


can any tell me why slope 40% and 80% is calculated in differential protection?

1431


What is difference between isolator and circuit breaker?

616


in control panel, how can i measuring the distance between one bus bar to another bus bar. then now only for bus bar. in mpcb and contactor also. that means one mpcb to another mpcb how much distance? how can i calculate that.

1835


what is class of SPD and dittels of all class ?

1573


how to calculate the earth fault current

1955


Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors

1440


Use of switch mode power converter in real-time basis?

625


what are the values of VRY,VYB,VBR,Vry,Vyb,Vbr,Vrn,Vyn,Vbn for Magenetic balance test of 100 KVA and 63 KVA Distribution transformer

2422


If we impress a dc voltage of 230 V on an unloaded 230 V, 50 Hz transformer it wi A give high secondary voltage B burn out C give secondary voltage as per K D none of these

1574