Answer Posted / nizam salih
A pole drop test can be done when the generator is in
standstill condition. Provide a ac voltage of 230V to the
rotor terminals of the salient pole machine and measure the
voltage drop in each pole. At least 5A should flow through
the rotor poles. A small current will not provide good
results. Once the voltage drops are recorded calculate the
drop index as follows.
Index = (max. value - min. value)/avearge value *100 %
An index value of less than 5% reprsents the poles are
good.
This is the usual annual test that we carry out in our
hydro generators.
Nizam Salih, Electrical Engineer, Sri Lanka.
| Is This Answer Correct ? | 10 Yes | 2 No |
Post New Answer View All Answers
Explain what cmos is and its benefits?
what is the difference between electrical and electronic choke?
Why is better to have a minimum ceiling voltage of 250% than 160%?
Why the frequency of ac in india is 50 hz but in some other countries it is 60 hz.
Difference between transition and diffusion capacitance
71ohm,111ohm,95ohm,179ohm in calculate the total ohm in series circuit
HOW TO CALCULATE EARTHING SIZING?
1.why we are using metal oxide gapless block in lightning arrester,2.What is minimum and maximum rating of metal oxide blocks using in india
What is size 00, 01, 1 etc., in HRC fuse types?
if 6 earth pit value is 1.5 ohm then what should be the number of earth pit to make the value .8 ohm
will there be any problem by recovering slip from single phase induction motors?
Show Details FROM:Muhammed Ikram TO:qa@allinterview.com Message flagged Saturday, June 4, 2011 10:07 PMMessage bodyHello all, i want to ask a question to all of you that what is VMM (voltage monitoring module )? how it work,s? i heard somewhere that it compare 1 phase voltage to other phase voltage. but there is also some setting on it. how to set it,s setting. please tell me briefly. Thank,s and Regard,s. Muhammed Ikram.
how can calculation ate Amps for cabel. Ex-for 1sqmm wire hou many amps we can draw
lorteny method
What is the criteria that generally follow by distribution licenses to fix contact demand of their industrial customers?