If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?
Answer Posted / k.prakashchandra
Let me cite an example.We have one 220/110 KV 100 MVA Auto
transformer.After 5 years of service ,it tripped with a
sound, on the following relay
indications.Diff,OS,Bucholtz,OC -R ph and EF (REFR not
provided).On meggering without test charging ,the results
were OK with LT R -body being higher.Then we resorted to
continuity test ,which indicated that LT R phase bushing
has been open circuited.On examination it was found that
the joint in the lead from R-phase winding to bushing was
severed due to bad workmanship.We did not conduct any other
tests.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how to calculate the formula of cable size if motor kw is given
how can we save enegry by using VFD for Resiprocating Air compressor which is having more unloading running hours
Why frequency changes due to load variation in power system ? i.e why when load increases frequency decreases?
Write down the name of 2 lady Bir Pratin of Bangladesh
i applied for the ap transco please forward the freqventley asked QA
What is quadrantal symmetry?
what is the effect of higher value of GD???
How to design pavement quality concrete by using C.R.C.P Method
how to identify vector group of three phase transformer by voltage method?
pls,send the previous year written test questions.
What is the tension required for the 25000 CFM AHU belt
While testing a ZCT what parameters have to check or measure?
1.Can we use 6.6/11KV 300sq mm xlpe 3core cable for LT use (415 Volt). 2. If we use it for LT then what is the current rating
PLEASE SEND ME NTPC RELATED INFORMATION LIKE WHICH TOPICS HAV MORE SCOPE,BOOKS TO READ,CUT OFF...PLEASE.mail at thiru.1203@gmail.com
If UG power cable both ends are to be earthed or what? If not why?