Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

sir
what is the minimum IR value of 11 KV alternator?

Answer Posted / md. m. u. noman

IN my traning preod i face this question.i have learn 2 mathod.
1st IR >= system voltage in M ohm +1 M ohm.
for example, 3.3kV motor IR= 3.3+1 =4.3M ohm....that means
greater or equel to 4.3M ohm..

2nd is IR >= (20*V)/(1000+2P)M ohm.(at 25 degree celcise)
where , V= rated voltage ofmotor;
p= power in kW......

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain the term parallel path in dc machin ?

2261


Why do we mostly prefer to generate and distribute electricity in 3 phase and not in 4 phase or 5 phase?

1255


I am apply the AAI. So i want electrical sample question paper in technical with answer my id is vijayjobsmart@gmail.com

2748


Why increase in current leads to increase in conductor temperature?

1183


Dear Sir/Madam, I have one questions we have three steam turbines and one Gas turbine and our industry linked with the public network, we have protection system one of the protection is reverse power we can export just four MW only i would like to ask about how to calculate the reverse power. Thank you in advance best regards

2139


What is the difference between single core 2 wire and single core 3 wire system? Which application we are using this? and for What purpose we are using this?

2385


In Electrical 'Single Line Diagram' cable nomenclature shows "2 X 1C X 630sq.mm to be provided for one incomer. The question is how many cable to be proved for one Incomer.

1819


can u give me a brief idea about power line carrier communication ??

2041


why does connected a indutor with mnsformeretering core of current transformer ?

2192


what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?

2178


What is the need for a controller?

1280


What is the difference between a 3 winding and 2 winding Potential Transformer

2339


what kelvin's law ?

2164


Why DG set is not installed in Terrace ??

1282


for 100 HP Induction motor service factor is 1.2(SF) we placed a VFD at the motor side load is balance with 0.3 Amp's Phase to Phase but at incoming of VFD load is un-balance with 10 to 20 Amp's what will be cause of load un balance

2010