Answer Posted / sahnis
First step is to isolate the trasmitter chamber from tank.
Close HP first and then LP. After that drain the Chamber by
opening drain valve on the bottom of the chamber. Then
connect a trasparent hose and keep it parallel to the
chamber to know the level inside the Transmitter chamber.
Then start filling the Fluid untill the low level. When the
low level reached, the zero adjustment( 4mA output from tx)
can be done by turning the zero adjustment screw. Then fill
the fluid upto highest level and turn the span to get 20mA.
Calibration is done and the instrument is now ready to be on
loop.
| Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
PT RTD Range: -200 to 500 degree celsius If I configured in DCS Lower range and Upper range . In face plate it shows red colour due to overa range how was the characteristics look If the temperature is more than operating range. how was the characteristics look . whether its in Resistance vs Temperature curve is Linear or Non linear
principle of automatic votage regulator
What is three element in drum level?
What is the difference between modbus,fieldbus & profibus
Pl send the model question paper of mahagenco account officer post
Any one can help me to identified, how can we interchange the device in FF
how to turbine speed measurement?
What is super thermocoupal?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
Explain types of valves?
what is the minimum power (P=VI)to produce a spark?
What is the start up procedure of desalter
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
I want to measure and control level in tank of size 10*5 filled with gasoline, so plz give me the solution with clear details. how to select transmitter and sensors.
how to calibrate 0- 150 psi presure gauge by dead weght tester