Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

On which side, taps are provided in tap changing
transformers and why?

Answer Posted / dilawar husain

The reasons given in above answers are correct. But there
is one more important reason and that is current. On Lv
side the current being more it needs heaviour contacts as
compared to HV side where the current is far less and
easier to handle. Also in case of ON LOAD Tap changers the
current is divirted to a bypass circuit for the duration
the tap is changing the pposition. This bypass circuit is
easier to design for lesser current on High voltage side.

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the basic elements used for modeling mechanical translational system?

1186


The moisture in air will condense at

1237


I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.

2145


from where the self excitrd induction generator get the power?why is the voltage regulation is poor of seig?

2350


Refernce currents are to be generated using refernce cueernts how can this be done??

2042


what are the ''pitting rings''and how cn they be controlled in a series generator

1894


xfhnchncv?

1959


Define demand factor?

1177


how can i get the formula to find out the cable size if i know the load of main fuse protection.

1984


what are the reasons of CT circuit faulty in busbar protection scheme?

1512


Why does an induction generator is preffered as compared to synchronous generator in especially a wind energy power production project?

2178


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2296


Why can't we take NO LOAD TRIAL of motors having V1 mounting??

1981


show the single line diagram of star delta starter with single phase preventer

4697


What is the rating of circuit breaker needed for 300 KVA load in 33 KV supply line in a transformer of 33 KV / 415 Volt ?

1822