If a Power Transformer Fails and the transformer
manufacturer suggest that "Do all electrical test on the
transformer?".
What are the test to be conducted in this condition?
Answer Posted / k.prakashchandra
Test No. 1 and 8 belong to life evaluation tests.As the tr
has been in use, tests No. 4 and 5 may not be necessary.For
Inter-turn short, test No .2 may prove useful if the
previous values are available and magnetic balance test (
No.1 )is really useful.Oil test is just for knowing the
present condition.If the tr has failed within the guarantee
period , we have to take extra care while furnishing the
test results. The firm may put the blame on you,for the
damages for applying the voltages to test.Simple tests and
relay operations are sufficient.It is more difficult to
prove that a tr is healthy by all means.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.
what is the common earth
Draw the equivalent circuit of crystal oscillator?
for 11KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV OH system what will be typical per KM "R" "L" "C" parameter. for 33KV UG system what will be typical per KM "R" "L" "C" parameter.
Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.
what is effect of leading power facter on the system and billing
What are the two basic types of transformers?
concept of busbar and load dispatching..?
what are the condition that makes hooter blow?
please send me the L&T Emb. sys. placement papers and entire details of pattren
What is the formula to calculate the rating of a three phase air circuit breaker
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected
how we test a 3 phase motor on single phase supply....? HOW WE RUN A 3 PHASE MOTOR ON SNIGLE PHASE. supply for testing..? how we verify of a 3 phase motors 6 wire & name thame a1/a2/a3..b1/b2/b3 and c1/c2/c3 for connecting star delta starter ........i have only 1 phase supply ? help forum..........
WILL SCHNEIDER MAKE ACB(MASTERPACT)TRIP ON REVERSE POWER?
What is the Designing & Selection Procedure for a DG/Transormer of rated capacity?