Dear sir,
we are getting voltage fluctuations suddenly for 2 or 3
minutes again it becomes normal. we checked each and every
connection some times we are getting 110 volts like that
from earth to neutral again it is reducing we are getting
supply from 45 kva DG set give earthing properly.
Answer Posted / manoj dubey
generally voltage between neutral and earth occurs when
there is unbalance distribution of load in all three
phases. first check load balancing on phases. also check is
there any single phase heavy load is switched ON at the
time when voltage increases between neutral and earth.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
HAI SENT HPCL APTITUDE QUESTION PAPER, MY EMAIL ID IS angus_eee04@rediffmail.com,angus_eee04@yahoo.com
hello friends..... any one have papers or any study materials?sail ,hpcl...?
if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?
what is ground fault in ACB?
Please elaborate th´evenin’s theorem?
Enlist four components of electrive drives.
What are the advantages and disadvantages of negative feed back?
how solar power plant energy meter multiplication factor
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
WHATIS TIME CONSTANT? WHATIS ITS SIGNIFICANCE? ILLUSTRATE THROUGH EXAMLES.
What is the difference between the impedance percent and impedance voltage ?
WHY IN AC DRIVES,INPUT PHASE CURRENT SHOW UNBALANCE?
Is it true that in the 3 phase transformer, the limbs of the core are at 45 dgrees to each other. if true, why?
How is magnetic leakage reduced?
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???