Answer Posted / karthigai selvan
in the field have to isolate first hp and lp side isolate
valves
fill the water on both side of both impulse tubes same time
both tubes should be in ambient(open to atmosphere) check
zero if not do zero trim then line up
thanks
| Is This Answer Correct ? | 9 Yes | 4 No |
Post New Answer View All Answers