Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
Why magnetic flux produces an induced current?? what is the detailed procedure ?? ans plz
Where is the best place to mount distribution panel in a house.
HOW TO DESIGN THE body EARTH cable(Copper Conductor) size for 60KVA UPS?
What is capacitance?
What is meant by coupling capacitor?
what is the difference between neutral and earth
What is the minimum distance to be maintained in between HT panel and LT panel and Instrument panel as per IEC and NEC standards?
role of europe union in UK safety legistlation (electrical safety)
What are the types of the glands and difference between single and double compression type of cable Glands.
why ct ,cvt should be stored in a vertical position?
What are the applications of different multistage amplifiers?Plz also write advantages of these amplifiers? Thaaaaaaaaanx
How to protect sensitive loads such as Dosing pumps inside a factory from voltage surge/voltage fluctuation.
How maesure earth neutral value & how much maximum value value required in between earth & neutral.
WHAT DO YOU MEAN THE DIFFERENT TYPE OF CURVES OF RELAY LIKE STANDARD INVERSE, VARY INVERSE, NORMAL INVERSE, LONG INVERSE ETC....
What is the HVDC Transmission System? What are the conditions applicable to lay an HVDC Line?