Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
which type of amplifiers are used in multimete?
What is the difference between cylindrical-type and sandwich-type winding?
For the requirement of a furnace of temperature range up to 1200 oC using silicon carbide rods, What is the required rate of transformer needed (please do it with all details)?
how to calculate single phase motor efficiency ?
I am going to appear for the RRB Chennai Section Engineer online exam. Please send me the question papers from 2001 to date to my mail id:upendrakrishna20@gmail.com,plz send me ,or send any other rrb papers plzzzzzzzzzzzzzzzzzz
why are u join ntpc
what is meant by LCR meter? where its useful ?
We have a distribution transformer of 750KVA/11kv/440v and an AVR (Servo Stabilizer) of 750KVA on the LT side of distribution transformer. Also we have an ACB of 1200A on the output of distribution transformer (that is on the input of AVR). We want to have an MCCB on the output of AVR. What should be the rating?
What mean by MLTP
how to get electrical supervisor competency certificate in gujarat. i did 3 year diploma in electrical
is the value of inductance depends upon the value of thitha in doubly excited machine??
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
describe the A.C. Generator Testing procedure
How to Calculate Current Rating of SDFU (Switch Disconnector Fuse unit) for Protectionof Capacitor Bank connected to Busbar of 800Amp,in LV side of 11/0.433KV, 250KVA Transformer?