Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
what is the defination of Cable database? What are the points are considered while preparing cable database? Is there any sample available for cable database?
If I want to replace a 26KW Slip ring Motor with a Squirrel Cage motor & Drive (for a Hoist Application). How can I approximate the Motor & Drive HP required in new Setup.
Is it possible to measure the voltage of a battery from a single terminal?
why dimmerstate always connected in star connection? what will happen if it connected in delta?
how is working bearing heater?
What is primary and backup protection?
Can any answer me ,What will be the range of C.T coil for L&T energy meter EM301 used for 180 kva DG set
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take
lamination figures
Define what is the function of anti-pumping in circuit breaker?
how dia of wire and angles are calculated for overhead shielding wire to protect substation equipment from lightening strokes???
wheather the size of windings in motor and generator are the same
what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?
transformer spections :: input voltage 0-110-230v; output volage 0-10-12-14v; amp=3A using CRNO CORE, capcaity=50VA primary turns = ? ; secondry turns =?
what is the most permissible winding temp when we conducting a generator load test?(condition no load)