what is the ground clearance of 400KV transmission line?

Answer Posted / k.prakashchandra

As per IE Rules 1956,for EHT line the clearance above ground
of the lowest conductor shall not be less than 5.2 m + 0.3 m
for every 33000 V or part thereof by which the voltage
exceeds 33000 V ,provided the minimum clearance along or
across any street shall not be less than 6.1 m. So for 400
KV line, it works out to be 8.8 m

Is This Answer Correct ?    49 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how can maintaince the acb contactor moveing and fixing kit

1587


EXPLAIN USE OF ROCKING ARRANGEMENT IN ELECTRIC HEATING?

1381


kindly send me 11KV MV motor differential protection procedure by primary injection method.

1025


acb(AIR CIRCUIT BREAKER)NOT CHARGING AUTO

1836


i will applied in 1U-1W on 440 volt primary delta side. what is the result of magtic balance test

1378






What are the different types of controllers?

650


100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.

1843


why the name trunking bus PT

2489


What's the difference between non break power supply and non break non short break power supply

1026


What is a dominant pole?

681


Instrument connected to a single phase supply

1250


what is ATS & RING MAIN UNIT in Distribution System?And its Function.

1506


Why efficiency of generator is higher than motor at a particular load?

1625


in what type of applications v can use q meter?

1669


During regenerative breaking= A rotating magnetic field is reversed B slip is positive C torque is positive D slip is negative

1517