What is the megger value for ht

Answer Posted / kota venkata rao

I coincide with the opinion that the thumb rule of KV+1 for
is not suitable for cables . For cables there shall be a
minimum value which shall be more than the value derived as
per the kv+1.The IR value varies with the operating
temperature. The value shall be high at at ambient
temperature and low at higher temperatures. However megaar
instrument 1 kv upto 1 kv rating and 2.5 kv to 5 kv upto
and including 33 kv

Is This Answer Correct ?    5 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how invertor convert the dc into ac give brif detail

1532


What do you mean by a phase angel of instrument transformer?

633


why asa method ZPF method is more accurate than ASA method?

5318


can you send me the placement papers of electrical engg. from companis like NTPC,DRDO,IOCL,HPCL,BPCL etc.?If,plz send as soon as possible.Thanks.

1677


State thevenin’s theorem?

656






1.what is mean by 8/20 micro sec waveshape

1788


WE HAVE THE DC RECTIFIER 1500A, INPUT VOLTAGE IS 3 PHASE. HOW TO CALICULATE THE LOAD? 3 PHASE SIDE EITHER dC SIDE. PLEASE SUGGEST ME

1401


i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.

1408


WTA used cb?

1437


How test for Ddo vector group test condition?

1961


Its possible to use 3core 2R of 240 sq.mm cable for 3phases & separely 50sq.mm 3core cable fully for Neutral for connection of PCC to MCC 3ph..4wire system?

1679


What will happen if the armature resistance is in minimum position and the field resistance is in maximum position while starting the motor

969


how can we understand that where we have to use ac or dc coil for solenoid valve and why?what is the different between coil of ac and dc explain please.

1486


please send me previous year questions of jspl through which i could prepare myself for the test.

1368


what are the problems that generally occur in power flows??

2536