1.what is the difference between MPCB and MCB ?
2.what is the difference between MPCB and MCCB ?
Answer Posted / george m s kingsley
Hai dear engineers,
MPCB- Motor Protection Circuit Breaker
It breaks the circuit depend upon the properties of the machine.
eg:- Set the breaking current of 10Amps in MPCB for the
Machine rating of 10Amps.
So that the machine take the starting current of 1.3 to 1.5
times from the rated.MPCB does not react here. But if the
current goes 120% to 150% based on time duration it breaks
the circuit.(overload relay supportive to machine)
MCB- Miniature Circuit Breaker.
It doesn't bother about Machine. If the Ampere goes more
than the MCB range it breaks the circuit.
Short circuit protection
(overload relay supportive to resistive, lighting load,
control circuit etc.)
Is This Answer Correct ? | 54 Yes | 10 No |
Post New Answer View All Answers
How to calculate loses in transformer of 160 KVA ?
Define cut-off rate?
How many types oil using in transformer ? How many letars using in transformer..?
hi friends i m from electrical branch and seeking for tech. + apti. both papers of hpcl plz get it available as soon as possible
What is step signal?
WHAT CAUSED THRESHOLD VOLTAGE TO EXIST?
How can we checked Killo Watts of Motor & Alternator?
how to set the time in digital timer ?
How can a equal potential zone be carried out in conductors?
What is knee point voltage?
As you achieve greater success with the company after some years, Will you like to be a share holder in our company?
What magnetic circuit is formed in berry-type constructions and why?
a starter used for squirrel cage induction motor?
What are IR values and what it should be for coil and for insulator
what is the use of expulsition protective gap in 11Kv line.