how does we do bench calibration of a differential
transmitter.
Answer Posted / himanshu amin
dp trasmitter is having range of few w/c. take example of
you want to calibrate 0-50 in h2o dp transmitter. connect
power supply and multimeter to connection point. connect
small hand pump to high side of dp transmitter. keep low
side of dp open to atmosphere. first check 4ma when both
connection are open to atmosphere. then connect hand pump
to high side and give 12.5, 25.0,37.5 & 50 in h20 and check
8,12,16,&20 ma o/p.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
how to calculate control valve bonnet size?? or how to select its material?
send me last 5 years questions asked in rrb chennai, for section engineer
how to control pid
What is Cavitation in a control valve?
In turbine, what does term CDP, NI, NH, HSSOC, means
Explain why use mmwc unit?
Tell about your IFFCO plant visit.
hi friends,im an instrumentation and contol engg student,can u hlp me of suggsting barc written question paper,my id is roysuvaranjan@gmail.com, cel no.9563591747
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
How will you test a transistor with a multimeter?
What is the purpose of LO Overhead tank in turbines.
There are many type of control cable like pair,core,tried, What are defination each one
What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.
how to calculate the total flow in square root