Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the technical diffrences of mccb and acb

Answer Posted / krishanu bhattacharya

Generally speaking, ACB are used as main incomer protection,
that means just after the transformer as the highest short
circuit current would be available just after the
transformer whereas MCCB are used as protection in outgoing
feeders where current rating & SC Breaking capacity needed
is a bit less than ACB. Though now a days MCCB and ACB both
can break a 100kA fault, but the main difference is:
ACB is category A breaker whereas MCCB is category B. that
means ACB can withstand the high SC current for a few
seconds so that the whole system will not trip just for a
small fault but in case of MCCB there is no withstand
capacity, if there is that too for ver smaal time in ms. So,
physical dimension of ACB are moere than MCCB. Thanks

Is This Answer Correct ?    23 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the difference between linear choke and suction choke?

2746


What is the difference between earthing,ground&nutral?

6706


I have a relay contact rated at 220v dc which is supplied with a 24vdc from the panel,for it to trip the dampers(24vdc).What if the application of the relay changes so that it should work at its rated 220vdc then will it work at 24vdc supply given or any other consideration needs to be taken .....

2099


i want to know how to determine that a surge arrester work properly in 11kv system. and how to test a 12kv surge arrester

2170


Is there any guideline say about display of earthing value near to earth pit

1209


why are u join ntpc

2173


which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?

2191


what is meant by neutral compensation factor and where it is used

1922


What is the purpose of using busbar mounting fuse?

2047


When color of silica gel will gets change from blue to pink from Top to bottom?

1608


what is meant by CT`s saturation ? Can we use Metering CT`s with Protetection CT`s ?

2194


what purose of the double circuit transmission line phase of the line phase changed for circuit-1 for Circuit-2 R-Y-B B-Y-R

2292


How we can calculate the life of Lead acid battery

1793


Is it required to use Automatic transfer Switch in L&T panel board if we use AMF panel with DG set? How the single line diagram will be? Please forward the material to sreenu_207@yahoo.co.in

4741


What test must you do before powering up a circuit that you have been working on?

1871