How to calculate the diesel generator efficiency? what
details are required to identify the running diesel
generator sets with 1000 kVA & 180 kVA?
Answer Posted / imran mazhar
You did not say what efficiency, whether you get good KWH/
diesel consumption or whether the genset is loaded
efficiently
Whatever, you need a KWH METER AND DIESEL CONSUMPTION
METER.If you run your 1000KVA gen set for 20 hrs.your
genset say at 0.8 pf it could have generated;
1000kva x 0.8 =800KWH per hr .SO FOR 20 Hrs s 16000KWH. If
YOUR KWH generated reading says 12000kwh than your
generator usage effiociency is 12000/16000 =75%
If the diesel consumption was 600ltrs than kwh/l is
12000/600 =20KWH/Litre diesel. you have to calculate
seperately for both of them.
| Is This Answer Correct ? | 18 Yes | 27 No |
Post New Answer View All Answers
Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?
r we are using in gas turbine mark (5) frame (6) (made in india Bhel 1997) Ā
Power Factor Correction Panel (Manual & Automatic)
If the earth is a good conductor of electricity, why don't people get shocked every time they walking on earth?
what is the current setting for different relay protection for transformer .
what is the differences between microprocessor and general purpose computer
i have interview in Pepsi company what type of question will ask please send the question and answeer
what are the parameters plays a major role in Potential transformer Burden calculation??
Give the expression for the frequency of oscillations in an op-amp sine wave oscillator?
what is meant by class 1 E in electrical power supply?
working of diesel generator ?
What is the Basic Difference bitween Long Shunt Connection and Short Shunt Connection in DC Generator?
Explain mechanical rotational system?
Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?
3ph motor running with unequal kw and different pf what are the reasons