What is the actual formula for transformer short circuit
test? below i given rating of the transformer..
1000KVA, pri 11KV, Pri amp 56A. %Z 5.95..

Answer Posted / k.prakashchandra

Isc=I(100/%x)=941.18A

Is This Answer Correct ?    4 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how unidirectional torque is produced in DC motor?

6287


what are the sample questions asking to the test cunducting for electrical superwising lisence test?

1653


What is trip and closing coil in cb? Why need of them

1007


WHAT IS counter flux IN CT?

1520


what is the difference between circular wdg & ractangular wdg?

1544






IF % IMPEDANCE OF A TRANSFORMER IS INCREASED FROM 5.8% TO 8% HOW MUCH THE EFFICIENCY OF THE TRANSFORMER WILL COME DOWN?

1963


what do u understand from filter factor of reactor?

1517


please tell me when we start motor without load in star or delta connection whose current above condition,pl write formula

1782


Either the Armoured Earthing strip of HT 3 core cable have to pass through CB CT or not , why ???

1541


What technology is used in latest generators?

1626


HOW CAN WE DECIDE THE SUPPLY VOLTAGE FOR MOTOR ACCORDING TO ITS RATING(IF ANYONE KNOWS GIVE IT WITH EXAMPLE AND ITS CALCULATIONS)

1501


2. A current i=(10+10 sin t)amperes is passed through MI type ammeter. its reading will be.........

1899


describe the constructional features of an auto transformer and its principle operation

1801


what is the circutor?why we use it ?

1822


how the synchronizing is obtained at bus couplers in grid substation? (because there we cannot change the frequency in one of transmission lines like in generator synchronization)

1846