I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-
1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.
What is the reason of spark?
Please explain the reason & rectification of above problems
Answer Posted / elangeswaran
pl check the type of load connected and if the secondary is
feeding a system of two sources with a buscoupler(three
pole) and neutral interconnected bus ultimatly neutral
voltage is above allowable level.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
HOW THE OLTC TRANSFORMER SAVE ENERGY IN COMPARISON TO OFF LINE TRANSFORMER AND IS IT ECONOMICAL TO REPLACE THE OFF LINE TRANSFORMER TO OLTC TRANSFORMER
What is polar plot?
how current is reverse from its normal direction during the fault?
is there any phase difference occurs while primary and secondary side mutual induction occurs?
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
What is the difference between acs 550 & acs 850
for a 400kv t/m line with 10 ampere current will corona occur?
what is saturation kit?which use above 15 kw motors panel side.
we have 3 single phase transformers. how will we generate 6 supply from 3 phase supply input
In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..
what kn of disc is used in 33kv,132kv,220kv,400kv,800kv transmission line
What are the types of windings present in the ceiling fan? What winding will be effective first when we started the fan?What are the resistance and inductance ratios comparatively at the initial speed and full speed of the fan?
what is the major difference between LIBBP & HIBBP.. which one is most preferable..
In TNC switch, is there any 1NO+1NC block ? and if we move over closing position, is ther any affect on trip position or vice versa?
y we use neutral,all r told its used to for closed path..k its a just used to closed path,in a transmission line y we put same conductor used n both phase and neutral..if we use less than phase conductor in neutral mean we ll reduce cost its right r wrong..if we use mean any problem occur in transmission line..