what is difference between 3 wire and 4 wire RTD sensor?
Answer Posted / sam.r
Most RTD’s incorporate a third wire with resistance R3.This
configuration provides one connection to one end and two to
the other end of the sensor. Connected to an instrument
designed to accept 3-wire input, compensation is achieved
for lead resistance and temperature change in lead
resistance. This is the most commonly used configuration.
If three identical type wires are used and their lengths are
equal, then R1 = R2 = R3. By measuring the resistance
through leads 1, 2 and the resistance element, a total
system resistance is measured (R1 + R2 + RE ). If the
resistance is also measured through leads 2 and 3 (R2 + R3),
we obtain the resistance of just the lead wires, and since
all lead wire resistances are equal, subtracting this value
(R2 + R3) from the total system resistance (R1 + R2 + RE)
leaves us with just RE, and an accurate temperature
measurement has been made.
A 4-wire configuration is also used. Two connections are
provided to each end of the sensor. This construction is
used for measurements of the highest precision.With the
4-wire configuration, the instrument will pass a constant
current (I) through the outer leads, 1 and 4.
The voltage drop is measured across the inner leads, 2 and
3. So from V = IR we learn the resistance of the element
alone, with no effect from the lead wire resistance. This
offers an advantage over 3-wire configurations only if
dissimilar lead wires are used, and this is rarely the case.
Still another configuration, now rare, is a standard 2-wire
configuration with a closed loop of wire alongside (Figure
5). This functions the same as the 3-wire configuration, but
uses an extra wire to do so. A separate pair of wires is
provided as a loop to provide compensation for lead
resistance and ambient changes in lead resistance.
| Is This Answer Correct ? | 21 Yes | 3 No |
Post New Answer View All Answers
How does temperature bath work? How does coil gets heated only by applying some current?
How many ohms are required for proper earthing?
What is furnace draft control?
plz send me general of ongc
I have got a call of IOCL interview for projects having 2yrs experience. What sort of questions should I expect in the interview?
Is it ok, to use non-contact type Radar type LT, on a tank that is half circular from the bottom side? If yes the, isn't the waves gonna bent in other directions?
this site is owned by an nonsense
what is basic difference between motion balance and force balance in pneumatic instrument?
how many types of spped sensors n vibration sensors?their basic principle n connection?
I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?
How to do gas analysers calibration in AUTO and Manually by using zero and span gas?
Explain the key components of control loop?
What is the formula of vabration sesore. i mean how to covert mils to volt plz share if any body knows very argent : my mai is merajalam143545@yahoo.com
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
please send the drdo exam paper