what is difference between 3 wire and 4 wire RTD sensor?

Answer Posted / sam.r

Most RTD’s incorporate a third wire with resistance R3.This
configuration provides one connection to one end and two to
the other end of the sensor. Connected to an instrument
designed to accept 3-wire input, compensation is achieved
for lead resistance and temperature change in lead
resistance. This is the most commonly used configuration.
If three identical type wires are used and their lengths are
equal, then R1 = R2 = R3. By measuring the resistance
through leads 1, 2 and the resistance element, a total
system resistance is measured (R1 + R2 + RE ). If the
resistance is also measured through leads 2 and 3 (R2 + R3),
we obtain the resistance of just the lead wires, and since
all lead wire resistances are equal, subtracting this value
(R2 + R3) from the total system resistance (R1 + R2 + RE)
leaves us with just RE, and an accurate temperature
measurement has been made.


A 4-wire configuration is also used. Two connections are
provided to each end of the sensor. This construction is
used for measurements of the highest precision.With the
4-wire configuration, the instrument will pass a constant
current (I) through the outer leads, 1 and 4.

The voltage drop is measured across the inner leads, 2 and
3. So from V = IR we learn the resistance of the element
alone, with no effect from the lead wire resistance. This
offers an advantage over 3-wire configurations only if
dissimilar lead wires are used, and this is rarely the case.

Still another configuration, now rare, is a standard 2-wire
configuration with a closed loop of wire alongside (Figure
5). This functions the same as the 3-wire configuration, but
uses an extra wire to do so. A separate pair of wires is
provided as a loop to provide compensation for lead
resistance and ambient changes in lead resistance.

Is This Answer Correct ?    21 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the input of digital counter during the the calibration time?

1827


How to check vortex flow meter is in good condition while we do not having calibration setup?

7499


Which type of diagphram use in costic line,DM water line,natural gas line,oil line?

3478


What is the diffrence between ff tx and non ff tx

2453


How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?

2013






why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2200


Name different types of bourdon tubes.

667


We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1134


Hi, I am Newely Joined in Construction company instrument engineer? Any one can Plz tell me How can I advanced preparation for Releated Engineering and construction Documents?

2149


How an rtd work, and what volts/current goes to a rtd to measure the resistance?

728


can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?

4281


why we are using drum level control valve air to close?

1596


Explain the key components of control loop?

564


List three types Level Gauges with their working principles

1637


why would you like to join our company

877