We have a 1275KVA existing Transformer in a power plant
project. Customer want to get it test & confirm whether it
is a Dyn1 Transformer or not. Pleae let me know how to test
it.
Answer Posted / mani_mc2006
If they are mentioned or not leave it. Check the following
condition.
1)1U2n + 1W2n = 1U1W
2)1W2v=1W2w
3)1V2w > 1V2v
If it is satisfied with above. Then sure it's Dyn1
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
What is reverse power relay?
Why the field rheostat is adjusted such that the voltmeter reads 380V
Why the power generated in dams is complex power? Why the generators in dams cannot produce Real power directly (i.e power which has zero reactive part)?
In DC generator, we use commutator, having no. of segments. Then how it is possible to get a half wave of voltage and current for half rotation of armature?
what is parellel power factor correction?
how to measure the transformer resistance values(dyn11)?and howmuch the minimum value?
Merits & Demarits of Oil circuit & Air circuit breakers ?
why current flow to the opposite direction of flow of electrons???????????
what is the relation between reactive power and power factor for the what is the limit of reactive power and power factor
What is the lockout relay
Explain how to determine capacitor tolerance codes?
how we control automatic generator i'e with to supply (main supply and local generator) when the main supply was break to supply the local supply automatically to begin supplying power.I now this control circuit is the combination of contactor time delay contactor switch and overload relay .but my question is how we combine those component thank you
what is the function of statics switch in ups and tell me parts
Apparent power is expressed as V * I(Conjugate). Why not in V * I ?
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?