does the power factor of an induction motor improve upon
used in parallel with a synchronous condenser , used
commonly to provide a leading kva ?
Answer Posted / rakesh
when a synchronous condenser is used in parallel with an
induction motor ( which normally operates at a low pf at
light loads) then the power supply to which an induction
motor is deriving its power from is relieved of providing
reactive power to im , while the im still draws the same
reactive power as before , the necessary kva is now
provided by the condenser as it exports reactive power.
hence the pf of im remains the same but the pf of the
combined system of im and sc is improved .
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
1.what is the funtion of chiller primary & scondary pumps. 2.what is the use of distribution lines & Types. 3.what is the use the thermal power stations & how much capacity.
When distance between two pulleys is not fixed, the tension of belt is adjusted by a) driver shaft b) driven shaft c) adjustment screw d) belt
How a capacitor discharge weld power supply works? what is the use of a pulse transformer?
Write down the name of 2 lady Bir Pratin of Bangladesh
DG Earth Value?
what type of questions are asked and howmwny questions belong this catagory?
What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?
what is the function of impulse relay
Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?
what is the use of piston rings in the engine used for a generator...........
iam working in power plant. In hot places tube lights are glowing at the end portion only. what is the reason for that?
Transformer how to maintaince a check b check c check d check
I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400
how to calulate short circuit current for the following: 1.cable connecting 11KV of 22KV/11KV transformer to 11Kv of 11KV/415V transformer 2.what cable size should i use.
I have a situation to design sub-Distribution board/Panel meant for feeding power sockets. In the incomer CAN i Take TP MCCB with Neutral Link and All the outgoing feeders with to sockets with TP MCCB and Neutral Link? P.S : My System is IT Earthing