I have 4 DG set with 1500KVA rating. system breakers are
11KV & alternator are 415 Volts. i want to Know what is
max. resistance for body earthing & 415 & 11KV V Neuteal
earthing. my fault current is 14 times for 2 sec.

Answer Posted / h r jadhav

body earthing resistance max limit is prescibed by
electricity rules 1956. in any case touch potential step
optetial shall not be more so the curent passing live body
more than 30 miliamp.in case of 415 volts max earth
resistance shall not be more than 3 ohms. and in case of 11
kv it is to be less than .6 ohn.

Is This Answer Correct ?    0 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how is working bearing heater?

1557


WHAT IS THE DIFFERENCE BETWEEN AN ACB & mccb 7 WHAT IS THE CRITERIA WHEN TO USE WHICH OF THE TWO

1830


In aerodynamic turbines which element is NOT there a.stator b.compressor c. Fuel intake system d.fans

1633


how can we change the phase angle b/w two phase?

4074


what is meant by skew width in machines?

1637






In HVDC LINE RECTIFIER CONTROL ON CONSTANT CURRENT AND INVERTER CONTROL CONSTANT EXITATION ANGLE CONTROL BUT HOW INVERTER CONTROL CONSTANT CURRENT?

1509


technically, what is the reason behind starting the motor star the delta connection .. and what other ways to do this rather than using " star-delta transformer"

1541


can we use engine degreaser for electrical motors?

1290


for what purpose the star point is done in ct

947


Is there any Electrical supervisor license which gives permit to work whole India rather than individual state??

1386


Whata are the types of Cables?

1589


Why does the rotor rotate?

1807


how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?

1548


When can we take Neutral as common neutral link?

1212


what is the excess air in furnace

1588