Answer Posted / www.islamqa.com
# The cascade control is a control strategy used to have
more stabilization in the control loop.
# Actually we don't need to wait till we have an error in
Pv to start the corrective action, the secondary controller
start responding for any small load disturbance, so we have
more predictable response and more stabilized loop.
# For the loop structure, we have the primary control loop
(master controller) give its o/p to the set point port of
the secondary control loop (slave controller) & the o/p of
secondary controller is connected with the final control
element.
# A good example for cascade is: any process with
controller and the final control element is a "valve with
positioner", here we have the secondary contoller is the
positioner itself which has a secondary closed loop with
the valve.
Regards,
Ahmed Sabry
Control and Instrumentation Engineer
GPC - General Petroleum Company
ahmedsabry.online@gmail.com
CELL.: 00 2 0121367310
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
How many types of sensor
for oil & gas industries which zone is normally preferred? why? give its example?
how to calculate control valve bonnet size?? or how to select its material?
Senior engineer's please help me, what is Loop Checking and Loop test? and write difference also? soon urgent
There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?
Regarding , there is an air cooler which control the fans(50% of AV FANS) by temperature in outlet , and the louver of Air cooler is controlled by HIC from control system , So if on Air cooler we will consider 2 individual I/P converter or positioner?
Explain the mechanism behind the turbine meter.
HOW CREATED LP & HP PRESURES IN DRUM FOR DRUM LEVEL MEASUREMENT!
PT RTD Range: -200 to 500 degree celsius If I configured in DCS Lower range and Upper range . In face plate it shows red colour due to overa range how was the characteristics look If the temperature is more than operating range. how was the characteristics look . whether its in Resistance vs Temperature curve is Linear or Non linear
what is the difference between scaler and vector drive
What is Droop? What is Step/Gradient Limiter in Turbine Governor control?
what is IEC code in cables & how to selecting cables?
Describe the typical instrumentation used in monitoring the performance of a shell and tube heat exchanger.
Introduce yourself which is not present in your biodata?
What you mean by multi stage control vavles?