when meggering a 3ph,480v oil reservoir heater on a regen
gas compressor, why do I get a reading to ground when
meggering phase to ground? shouldn't it read opened or is
there something that makes it read closed? on the same
heater, when ohming, it reads open. thanx

Answer Posted / k.prakashchandra

The resistance between phase to ground is in mega ohms if
star point is not earthed.

Is This Answer Correct ?    3 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is transformor oil gread

1963


upto how many load can v connect to stabilizer which is used for tv

1723


why u r living from presentaly working.

1955


why in a swquence network representation, the negetive sequence generated voltage is taken as zero?

1497


Define step response?

645






any one can explain the stages of a knee point which is taken during ct magnetising curve.

1315


Brief me about maintenance planning & sheduling of machine tool.

1702


ratings of lightning arrester

1617


what are the application of over current relay?

4218


TRANSFORMERS WITH DC SUPPLY

1518


why the neutral line is not giving shock to us if we touch it ?

1336


what is is the potential diffrence between two phase ?

5358


What will be in Mahagenco Trade Test Exam? I want to know the same.

3199


During Starter Panel Com missing I Found The Main Incomer 40Amp MCB 10KA Trip When Motor Change Star To Delta Motor Rating 20HP BUT When We Use Same MCB To Other Motor It Does Not trip Or What Is Necessaries for Star Delta Starter MCB SFU MPCB OR MCCB And What are The Breaking Capacity of MCCB in the Motor above 15HP

1399


A parallel flow heat exchanger will perform better than a counter flow heat exchanger. State if the statement is true or false.

763