Answer Posted / sdvyas,chartered engineer
Whenver any large inductive load like large rating motors
or capacitor bank is energised ,due to high inrush current
the voltage drop in the cable/line took place this result
into voltage dip in the system. Also, in case of fault in
electrical network the current shoot up extremely high and
voltage dip in the system may be noticed.
Voltage swell may be observed when inductive load on the
electrical network is suddenly thrown off as the energy
stored in the motor( inductive in nature ) can not last in
a very short time as the inductor takes times to last its
energy.In this situation 1/2 LISquare= 1/2 Cv Square and
voltage starts increasing. Other reason of voltage swell is
the lightening. During lightening, voltage induced in the
conductor may be superimosed on the power frequency and
this may lead to swell in voltage.
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
If any HVDC line is going with positive & negative(the negative usually have return path of current with earthing electrode). Now the question is if this HVDC earthed electrode which is using as return path and earthed any nearby 400kv or 220kv AC substation equipments. which will be the impact of this on AC substation & its equipment, how severe may be this and what should be the minimum distance require between HVDC earthed electrode and AC substation equipments? It's really an high engineering level question...Dare to answer and increase your knowledge.
- two pumps must work with them at the same time but if the first pump start the second pump must delayed for some time to start also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it
mccb service sittings be done?
Is there chopping current in resistive circuit
after how many spot we must chang secondry cable in portable spot welding gun?
While testing LA mast,What are the parameter limits ?
i want to run 11kv star connected motor in 6.6kv with delta connected throught inverter, is it possible?
Why are iron cores in transformers made laminated?
After synchronization with grid what is the demand value QKVAR and how we will maintain that?
hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E
What happened when capacitor connect series in ac circuit?
How to calculate pitch, gauge of winding wire, and No. of turns for 30HP, 3 phase, 4 poles 50Hz, 380V induction motors
how to calculate the settings for shaft ct protn in hydro generators
Single line diagram for dbb (double bus bar)system.
Dear friends I want to design busbar for1600 kva transformer(i.e2100 amps) what are all the factors to be considered before selectinga busbar what are all the standard sizes of busbars what is the formula for finding current of copper and aluminium busbar