Answer Posted / santosh nanavati
We are doing the impulse tubing work on HP &/LP side DP
transmitter for level measurement of atmospheric close or
open vessel as per the process application. If the LP side
of tubing is filled with suitable fluid (water or process
fluid), it is called wet leg. Under this circumtances, the
transmitter zero condition will be towards negative
pressure range equivalent to the pressure head of filled
fluid in the LP side tubing. Vice versa if side of tubing
is not filled any fluid & kept empty i.e.dry, it is called
as dry leg. Under this condition,the transmitter zero
condition will not be towards negative pressure range.
Is This Answer Correct ? | 16 Yes | 3 No |
Post New Answer View All Answers
what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail
What is the start up procedure of desalter
What do you know about gail?
How will you calibrate an Absolute Pr.Transmitter of range 400mmHg absolute ?
Explain about safety integrated level protection? . How it was differ from other protections ?
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance
What is the diffrence between digital signal processing and discrete signal processing?
Draw a simple circuit for a well head control panel used to protect the well against fire, leak, blockage, ESD, & controls the operation of one downhole & one surface safety valve. Explain the operation and controls
What is 3 element control system
Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.
What are the application of bernoulli’s theorem?
why we use 3 wire rtd direct wiring for temperature measurement instead of temperature transmitter like bearing temperature
How to Calibrate Level Troll in field
How to calibration a control valve?