Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

why the motor is rated as kw& transformer as kva

Answer Posted / nilkanth tailor

Transformer and genrator PF depends on the nature of
connected load ( Motor ), But motor has its own fixed Power
factor

Therefore Transformer and genrator capacity shown in KVA
and motor Capacity shows in KW........SO...if we want to
measure PF in GEN and TRAN...we require current and voltage
rating...so thier is in KVA....

but motor PF is constant so thier is no need to indiacte in
kva....so.......

Is This Answer Correct ?    4 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The power supplied to a 50mH inductor from a 120V, 60Hz source will be

4842


A 100W electric lamp is supplied from a 115V, 60HZ source. The peak instantaneous power dissipated in the lamp filament is

2447


im working in one private compeny in gujarat. i was complet diploma electric in 2010 from gujarat technical board. now i want electric supervisor licence in gujarat but i dont't know when i apply? plz give me address of the licence dippartment office in gujarat. gandhinagar

1914


diff. between tension mode & speed mode

2389


What happens if we run alternator on under frequency? 

2170


what is the series parallel connection of capacitors? and how can we use these application in three phase motors for controlling torque?

2158


A jet of fluid strikes a plate What was the force required to counter it?

1916


Dear sir, my knowledge about cable size determination is limited. Though I read examples I could not calculate the Cable size required for electric driven pump 40 KW, 380 Volt, 50 HZ, 50 meter from transformer and it is three phase star delta starting. Please help as there is no one in my surroundings to help.

1801


What is the difference between resistance grounding system and resistance earthing system?

1163


please send me privious exam's queation papers of section engineer(electrical).

2109


What is slope...? Explain slope 1 and slope 2...?

1659


can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?

3333


Can I use star delta connected induction motor for dual supply voltage?

2003


does a DG set has low fault level as compared to that of a transformer.If yes then why.

2026


how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?

2090