in our transmisison sub station why we step down firstly
132kv\33kv then 33kv to 11kv. can we direct step down 132kv
to 11kv.
Answer Posted / sudhir a kadam
usually this is done looking into the practical
requirements and availability of the transmission line. It
is not at all necessary that the HV 132 should be stepped
down to 33 KV. It can very well be directly stepped down to
11 KV. If we have a dual reqmt of 33 as well as 11KV.
132/33/11KV( pri/sec/ter) can also be designed.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Why do we apply both Differential and REF (HV and LV) protection schemes on YNyn configuration of a transformer?
WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION
dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour
What is the dc grounding system and what is diff between AC/DC grounding system?
what is diff btw electric,magnetic & eletromagnetic field
what are the factors to be considered while design the breaker either HT or LT??
what is meant by impedance & transient protection?
what does mean of RCT and STR in diffrential CT?
What kind of maintenance is conducted for Transformer
what is auto re-closer?
Q: How to calculate Transformer losses , tell us by Formula.
(1)WHAT HAPPENS WHEN SUDDENLY LOAD GIVEN TO THE INDUCTION MOTOR ? (2)CAN WE MAKE WOOD AS MAGNET ? (3)WHAT IS THE VALUE OF MAGNETIC FLUX DENSITY IN TRANSFORMER ? (4)WHY WE ARE USING ELECTROMAGNETI NOT ELECTROSTATIC IN MACHINE ?
can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??
Is phenomenon of resonance is harmfull fr the machine? if not or if yes please explain it?
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?