Hi friends, from Aug 4th onwards iam getting spikes for
analog inputs in our DCS for a period of 800ms. I throughly
checked every thing, finally i found that the DI, DO's from
MCC panels shields are terminated in the Signal Earth where
Analog Input signals shields are terminated. Is there any
problem with this type of termination?. i checked the
induction voltage from MCC and getting around 25VAC, please
suggest me in this concern. Our plant is 8months old only.
DCS is Siemens Make Simatic PCS7, and the transmitters are
Yokogawa make.
Answer Posted / sankarithi
Hi Friends only problem is due to earth pit. I throughly
checked every thing, finally i found that the Earth pit
totally became dry. I serviced the pit,Now there is no
spikes.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
can you provide me full detail about instrumentation in ONGC??
hi sir yhis is zahid ali i am preparing for the jspl at oct.4.please send me the recently updated sample paper.
Questions on flow meters,few questions on HART protocol,
What is modbus?
what is the electrical operation procedure for switching on 27.6MVA electric furnace.
i need some objective type questions in instrumentation
when a magnet is heated?
How does work A temperature valve or fv control valve in process plz brief me
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?
NSV type probe stands for
How can measure flow in oil line?which type of transmitter is generally used?
What is the use of gauge?
Any body have know try work calculation ???
What is the purpose of the analyzer in petrochemical plant?