Whether the DP transmitter can be utilised in the medium of
Vaccum for the measurement of Level?
Answer Posted / sankarithi
Hi Friends i finally succeeded to take the DP transmitter
into line for the Measurement of Level which is under
vaccum. The following steps to be followed.
1. Transmitter range should be in Positive side only.
2. Transmitter HP should be connected with the Level
chamber bottom side and maintain very less gap between
Level Chamber and Trasmitter HP end.
3. Connect Transmitter LP end with the Level Chamber Top
End and elevate the Pipe line 11/2 mtr above the tank level
in order to ensure that there will not any water entrance
into the LP side impulse line. We need to maintain LP side
without water.
4. All Joints should be tight and there will not be any
leakages.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,
what is difference between HOT permit and cold permit
How hart protocol can be connected with control valves?
Explain why use mmwc unit?
Explain PID controller tuning & any one method used for it.
Calibration of controller (pneumatic)
How to calibrate level transmitter with use of HART?
How to erection of DCS Panel at site step by step
Please can anybody help for control valve sizing step by step procedure?
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
How is flow measured in square root?
what are the use of belew gear in general ??
what is stroke check for field instument transmetter's & AOV's
what is performance test.need defination