Answer Posted / guest
1.Fix the transmitter on the process line and connect the
power supply.
2.Connect the impulse line to the transmitter.
3.Ensure level transmitter HP and LP main isolation valve
is closed.
4.Open the HP and LP valve and close the equiliser valve to
the transmitter.
5.Close the vent plug to the transmitter.
6.fill the water (condensate pot via) on LP side of the
transmittre impulse line.
7.Ensure transmitter display showing is zero.
8.If not showing zero,release the air lock (vent plug via).
9.Open the HP and LP main isolation valve.
10.Ensure the level transmitter working is normal.
Is This Answer Correct ? | 10 Yes | 3 No |