FOR ELECTRICAL TRANSMISSION TOWER WHAT SHOULD BE THE MINIMUM
HEIGHT FROM THE GROUND? AND WHAT SHOULD BE THE DISTANCE
BETWEEN THE TWO CONDUCTOR?
Answer Posted / k.prakashchandra
For extra high tension tr lines, the minimum clearance is
not less than 5.2 mtr+ 0.3 mtr for every 33 Kv or part
thereof by which the voltage of the line exceedes 33
Kv,provided that the minimum clearance along or across the
road shall not be less than 6.1 mtr.Clearances between
conductors for 66 Kv 75 cm,110 Kv- 125 cm ,132-160cm,220-
210 cm and 400Kv-410 cm
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control
What are the types of the glands and difference between single and double compression type of cable Glands.
why fractional pitch winding generally used in alternators?
how hazordious area is classified at an oil & gas plant and categorise suitable class of electric equipment in that area like induction motors, LCS, Lighting Fixtures Fluerescent/Flood lights Mercury& sodium lights, J.Bs, Power Cables etc
Explain the method to keep noises low in a control system?
I Want randstand placement papers
what is upper impedance and lower impedance of a distance relay
List the power rating of any 5 important electrical appliances used in houses.
how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.
how to calculate IR value of 33KV cable ??
how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
What is q factor?
how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec.
Mention the disadvantages of low power factor? How can it be improved?