Why current flows in nutral? As per theory there should be
no current in 3 ph explain.
Answer Posted / ujjwal karki
1. As per the theory, No current should be flowing in the neutral. But this is theoretically possible when the load in each phase are perfectly balanced. As the switching patterns of each loads in 3 phases are not exactly the same, some amount of neutral current is likely to flow through the neutral.
2.Another likely cause as to why there is current flowing in the neutral is due to the effect of harmonics. Lets take an example of transformer. The Hysteresis loss in transformer causes a non-sinusoidal exciting current to flow which mainly comprises of third and fifth harmonics. Since the line-line third harmonic voltage is zero, these current can only flow through the neutral wire or around the mesh winding.(If these harmonic current donot get a path to flow, the flux in transformer is not sinusoidal and the output voltage is non sinusoidal as well!!). Hence, high current might be flowing in neutral and there is even the provision of doubling the size of neutral wire to prevent its overheating.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Explain the role of a car driver as one of a feedback mechanism.
how can motor both beasrings insulation resistance can be check?
If we have 11 kv RYB Phase single core cable near about. Then wht effect and losses
I want d.g.set our company
I have made a 3 phase thyristor full bridge rectifier. But at the moment it is working only for the half bridge operation. Both the half bridges are on operation separately but when i put it into full bridge operation the oscilloscope output is zero. I rechecked that the pulses are correct for each thyristor. what could be the possible reason for this?
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
How to calculate the efficiency of Turbo Generator(Alternator) in general....?
What is the reason for using a GE G101 MCB in place of an EP102 MCB if both are capable of AC circuit protection?
What is contract demand in solar system?
What is the purpose of using busbar mounting fuse?
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??
why the protection turbo generators is most complex?
how flow current in 220 kv line to line
Difference between Earthing Truck & Earthing trolly for HT panel
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV