Answer Posted / jeffrey tay
U0 is the cable conductor and shield design with metal
cover layer or between the rated power frequency voltage; U
is a cable designed for use between conductors rated
frequency voltage (three-phase line voltage); Um is the
maximum operating voltage of the system; Up is cable
designed for use in each line of core and shield or metal
sleeve Lightning impulse withstand voltage between the
peak.
U0 value is based on cable systems where the single-phase
ground fault occurs when the duration of the permit
determined. In the GB 12706. 1 -91 stipulated in the two
types of cables: Category 1 cables, U0 for 21 kV, for each
single-phase ground fault time is not greater than 1 min of
the system can be used for single-phase ground fault time
of the most length of no more than 8 h, an annual total of
no more than 125 h of the system; Class 2 cable, U0 for 26
kV, for a longer ground fault systems, and cable insulation
performance requirements for high occasions.
Is This Answer Correct ? | 5 Yes | 5 No |
Post New Answer View All Answers
I have an existing old MCCB. ABB Model SACE, the rating are: Ue = 660 volts, Iu =1250 Amps, 3 poles, Ith (max) =800 amps at 45 deg C. I need a circuit breaker for my 3 phase motors, 380 volts 60 hz. the supplier required the minimum ampacity of the breaker to be 911 amps. can i use this breaker with rating of Iu =1250 amps but Ith = 800amps maximum?
How can eliminate noise problem inside temperature controller temp. variation due to contactor chattering problem.
why we are using Load factor?
Why we find the sensitivity for the CT's to check?
What is the suitable transmission voltage?
What is the use of lag compensator?
what is distribution board?
What is difference is of VSD,VFD,VSDS, are they the same as the direct current to control dc using above mention
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
draw 3 phase rectifier diagram
I COMPLITED MY B.TECH AND 10TH CLASS WITH 70%MARKS BUT 12TH CLASS 55%MARKS..CAN I GET INDIAN RAILWAY RECUREMENT EXAMINATION?
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
what are the types of electromagnetic forces developed in practical transformer?
Which standard we are following earthing resistance test
hi frnz,can somebody give me any project work? i am a 2nd year student & interested in practical works...plz give me some projects