my 10 hp submersible pump is tripping when connected
through ELCB.I have checked the megger value of the coil's
with body.It was found to be 0.2mega ohm.that is leakage is
there.But when connected to mccb it is not tripping.no
leakage current in the motor.Is it safe to connect to mccb?
what are the problem's will arise if future?also tell me in
ELCB no neutral is connected to motor.than how ELCB was
working?
Answer Posted / virendra joshi
There may be a minor leakage in , also please check the
mAmp of the ElCB if it is 100ma then there is a possible
chance of tripping on minor leakage.. i suggest you to try
with 300ma ELCB even if get tips then you have to check the
motor winding & connecting cable thoroly.
Is This Answer Correct ? | 9 Yes | 1 No |
Post New Answer View All Answers
I want the details about BHEL company examination.Can anyone able to help me please.
What should be setting for alarm,tripping and cooling fan on for power transformer's oil temp. and winding temp. indicator?
v/f drive basic princeple
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
What is the difference between resistance grounding system and resistance earthing system?
A jet of fluid strikes a plate What was the force required to counter it?
How to size fuse? How to size MCB?
what is level 2 automation?
HOW DO I CALCULATE THE SETTINGS FOR THE DIFFERENTIAL PROTECTION OF A 12kV/6.6kV, 6MVA,DYN11 XMER WITH PRIMARY SIDE CTR 400/1 AND SEC SIDE CTR 600/1?
nwhat are the main Components of servo motor?
what is gridrotor resistance starter
a simple c++ program to calculate simple interst with its data members as private
What are the advantage of free wheeling diode in a full wave rectifier?
when elecromagnatic waves are propogated in a wave guide?
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)