why generating power plant operating at above 0.9 lag?
detail explaination?
Answer Posted / sanu chaudhary
armature current of alternator depends upon the power
factor of machine .AT THE UNITY POWER FACTOR armature
current is minimum ,armature current of machine will
increse for same power if power factor of machine is
lagging as well as leading so it is desired to run the
machine near the unity power factor for optimum utilisation
of capacity of machine .in the leadind power factor machine
take reactive power from the infinte bus or grid and
machine is under excitation so it may be the cause of
panelty from power corporation due to reaciving of reactive
power hence we operate the machine near .9 lagging power
factor
Is This Answer Correct ? | 8 Yes | 4 No |
Post New Answer View All Answers
why output is out of phase in case of common emitter?
What is the maximum No. of out going mccbs permitted from an LV distribution paqnel? What is the ampere relation between incomer and out going switch gears/mccbs?
define superposition theorem thevnin theorem ,norton theorom?
How to calculate Ith (I thermal) for curent transformer
how could we know the size of cable by physical view?
After completing iti in electrician, how can i get certificate of electrical supervisor? What ia requirements. For it?
Why power genaration in India is at 50HZ while America its 60HZ
is that a problem if i connect a single phase load to a secondry delta connected transformer but i get a neutral from other transformer i the system?
At what factor resistance r of a conductor depends?
What are the different circuits in thermal power plant?
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
What is the abbreviation of NGT panel
what are the different kind of cables used for transmissions?
how to test YNyn0 vector group in transformer?
HOW DO YOU CAN CHECK A 15KV DIODE, WHETHER IT IS OK OR NOT?