When measuring the Insulation resistance of a motor winding
(winding to earth) using a megger meter, Applied
voltage(1000V) was automatically reduced to 500V. and the
measured insulation resistance values are also very low (in
Kohm range) Can anyone give me a reason???
Answer Posted / sridhar
there are two reasons of getting the value low.
1. due to moisture in the motor
2. winding has become weak
to overcome these problems the methods can be adopted
1. heater or halogen lamp to be provided near to the
winding of the motor to bring the resistance value as per
std.
2. by this above method, the insulation resistance is not
upto the mark, the same winding can be overhauled to
achieve the required insulation resistance value.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
1. transformer design formula ? 2. how to calculate the primary turns and secondry turns ? 3. core types ? 4. how to find the primary current and secondry current ? 5. how to calculate the stacking factor ? 6. range of fulx density ?
Write the force balance equation of ideal dashpot element.
can any one tell me about the Extra low voltage systems?From where we give supply to these type of systems??
Why corona leads to production of Ozone and glow of the color VOILET?
what is data block in plc ? How the values of data block are written and read by hmi ? what is the difference between function and function block ?
what is mean by restructuring power system?
what are the parameters plays a major role in Potential transformer Burden calculation??
Explain the difference between verilog task and verilog function?
Why can't we parallel the secondary circuits of two voltage transformers?
what is Anti-pumping?
How is the connection of the tap changer on the HV side been made?
what are the condition that makes hooter blow?
What is marx circuit?
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
Minimum IR value of 1.1 kv grade 3.5c (300, 240,185,150,120,95,70,50,35,25) sqmm Aluminium XLPE cable and 4c (16, 10,6 & 4) sqmm cu arm cable between RY,YB,BR,RN,YN,BN,RE,YE,BE & NE.