What is loop checking ?
Answer Posted / nachiket dani
Usually used term in Distributed Control System design-
after the logic for the process has been programmed into
the DCS software,the controller cabinet alongwith the IO
modules is interfaced to the server on which the logic
resides.The IOs are assigned as required and circuit
continuity check is carried out-LOOP CHECKING..Outputs are
forced to some value(universal) or forced high(binary) and
the signal level is checked at the output Terminal block of
the IO module.Similarly for Input checks, Voltage/Current
is fed via a calibrator at the Input Terminal Block (1 by
1) and signal is detected via the monitoring mode on the
DCS software..This is to ensure circuit continuity and
scaling(signal limits)-it requires time and usually done as
pre-FAT or FAT procedure.
| Is This Answer Correct ? | 42 Yes | 15 No |
Post New Answer View All Answers
how do we commission inergen system?
Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,
What is the difference between uv and ir scanners? and what is the workig principle of both
How to calibration coriolis flow meter?
What is the main difference between Cavitation and Flashing?
what is the diffrence between pressure safety valve & pressure relief valve....pls
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
how to turbine speed measurement?
what is your eligibility criteria for freashers?
How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?
in mass flow meter what is drive friquancy ?
Draw a complete P&ID of a flow suction tank indicating all control & protection equipment. Indicate all its inlets and outlets. Explain the controls for this system
can any send me a forbes marshall dtron 316 manual
How r the calculation of process line mpm.
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.