Answer Posted / rithesh
I/P converter - all the instrument calibration principal
will be same. In beanch calibration we have to give
pnumatic input of instrument air/ nitrogen with pressure of
1.4 bar or kg/cm2 or 21 psi and we have to fix a test gauge
of 0 to 1.5 bar(kg/cm2)/ 0 to 20psi at pnumatic output. now
we have to connect mA source to I/P converter. we have vary
the mA 4 to 20. the result will be like this.
input 4mA output will be 0.2 bar(kg/cm2) / 3 psi
input 8mA output will be 0.4 bar(kg/cm2) / 6 psi
input 12mA output will be 0.6 bar(kg/cm2) / 9 psi
input 16mA output will be 0.8 bar(kg/cm2) / 12 psi
input 20mA output will be 1 bar(kg/cm2) / 15 psi
if output not match with input we have to set things by
adjesting Zero and Span adjesting point.
| Is This Answer Correct ? | 21 Yes | 3 No |
Post New Answer View All Answers
what is the working principal of pribe
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
types of cable..? Use of every types of cable..?
please someone tell me what is function of vibration sencer and how many types and how to control viberation.please. my id is jimmykhan077@gmail.com
how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.
how to rectify the poor signal strength in utrasonic digtial flow meter ,model:ge digital xce868i
draw shematic diagram of c/v positioner(smart type)?
how to calibrate electro pneumatic positioner 8013 mil controls ltd ?gsr
What is surge and how is it prevented, what is the purpose of bypass valve across AS valve.
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
What are different type of instrument cable
the output of the common trasmitter protocol in qatar gas are the following