Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the significance of KV & MVA rating of the
transformer and how they are related.

Answer Posted / eduardo

kV means kilo Volts, and is 1000 V. So 10kV means 10 000V.
This is the operating voltage. You must have another voltage
in the transformer. One is for the primary, and the other
for the secondary.

MVA means Mega Volt Ampere and is the power of the transformer.
1 MVA = 1 000 000 VA.

For example. If you have a transformer 10kV/400V and with 1
MVA, this means that at full charge is able to delivery in
the secodanry 1 000 000 VA / 400 V = 2 500 A.
He must be connect at a power line 10 kV and will delivery
400 V (till the load of the seconary reach 2 500A, after
that the value of the tension in the secondary begins to
drop, but this is another story).
In the primary the current will be 1 000 000 VA / 10 000 V =
100 A (at full charge).

Is This Answer Correct ?    25 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is servo lock in CNC how they work and if any parameter for them in CNC machine

5301


WHAT IS FAULT CAPACITY OF HT MOTOR TERMINAL BLOCK? ANY BODY HAVE ANSWER PLZ....POST IT.

2144


what r substations?what r there work?why voltages r incresed and then reduced during distribution of power

1871


what is accuracy ? in any meters , coils accuracy . how can u defined that ?

2370


We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks

1999


The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is

1073


what is the advantage of connecting capacitors in delta than in star?

2044


As we use capacitor bank in 3ph ckt to improve PF, can we use capacitor in single ph domestric use, in house we have Fan,Mixer,electric cooker,iron,tube choke they also lag the system,because it is inductive load. if it is possible to improve PF of single ph system-- if yes- type of capacitor to be used,connection diagram, working in detail. if no-- list it.

1707


hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.

1947


What is meant by vector group

2438


In the magnetic fluxes, what is the role of armature reaction?

1099


8. A DYNAMOMETER TYPE WATTMETER RESPONDS TO THE.......

9175


IN dc capacitive reactance is??

1343


'documenˁ

1918


IN 1000kva transformer where the oil and winding temperature sensors is connected

2463