what is the significance of KV & MVA rating of the
transformer and how they are related.
Answer Posted / eduardo
kV means kilo Volts, and is 1000 V. So 10kV means 10 000V.
This is the operating voltage. You must have another voltage
in the transformer. One is for the primary, and the other
for the secondary.
MVA means Mega Volt Ampere and is the power of the transformer.
1 MVA = 1 000 000 VA.
For example. If you have a transformer 10kV/400V and with 1
MVA, this means that at full charge is able to delivery in
the secodanry 1 000 000 VA / 400 V = 2 500 A.
He must be connect at a power line 10 kV and will delivery
400 V (till the load of the seconary reach 2 500A, after
that the value of the tension in the secondary begins to
drop, but this is another story).
In the primary the current will be 1 000 000 VA / 10 000 V =
100 A (at full charge).
Is This Answer Correct ? | 25 Yes | 24 No |
Post New Answer View All Answers
What is the formula to calculate the rating of a three phase miniature circuit breaker
what is the Earth Voltages in Power Plants, Sub-stations, Industries, Residential & Commercial Buildings.
What is force on parallel conductors ?
What is icu and ics in Acb and how many time icu or ics passes from breaker?
What is the meaning of C1, C61, C91 cable
Hi everyone. Some Generators uses 3-Pole breakers with extra contactors for Neutral. Some uses 4-Pole. Why so? What is the idea behind this? Thanks in advance for the solution. Kr.
What are the advantage of free wheeling diode in a full wave rectifier?
at work i have a genertor/alternater what is the easyest way to work out if it is dc or ac?
What difference between ref protection and differential protection ?
advantages and disadvantages of inverse definite minimum time RELAY
why transformer tank is in rectangular shape what happen when it is in step shape
what is the difference between delta delta and star delta connection transformer? why we use delta delta transformer since it need earthing transformer for grounding?
There is air in a room . the top and bottom of the room are at constant temp. T1 and T2. DRAW THE temp profiles if a. T1 greater than T2 b. T1 less than T2
If a surge divertor is required to be protected by 32 amp C Curve Circuit breaker does this limit the amount of protection from surges that you will acheive
Classify driling machines.