Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the significance of KV & MVA rating of the
transformer and how they are related.

Answer Posted / eduardo

kV means kilo Volts, and is 1000 V. So 10kV means 10 000V.
This is the operating voltage. You must have another voltage
in the transformer. One is for the primary, and the other
for the secondary.

MVA means Mega Volt Ampere and is the power of the transformer.
1 MVA = 1 000 000 VA.

For example. If you have a transformer 10kV/400V and with 1
MVA, this means that at full charge is able to delivery in
the secodanry 1 000 000 VA / 400 V = 2 500 A.
He must be connect at a power line 10 kV and will delivery
400 V (till the load of the seconary reach 2 500A, after
that the value of the tension in the secondary begins to
drop, but this is another story).
In the primary the current will be 1 000 000 VA / 10 000 V =
100 A (at full charge).

Is This Answer Correct ?    25 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the synchronous timer ? and it applications.

2401


I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?

1755


kVA rating of ordinary transformer is increased when connected as an auto transformer because A transformation ratio increased B secondary voltage increased C energy is transferred both inductively and conductively D secondary current increased

2664


please send me previous year questions of jspl through which i could prepare myself for the test.

1878


can u give me a brief idea about power line carrier communication ??

1850


how we can set the IDMT relay.

2218


What si the d/f b/w KVA & KWH, kvarh & kvar, kwh & kvar phase voltage & line voltage

6167


what is the difference between the characteristics of two different phase bushing of any transformer

1812


Is the installation of the filter cloths necessary before spreading the gravels at the transformer yards?

1947


I am abt to give IOCL intrv.Plz sir guide me for IOCL intrvw (Electrical).Which subject to be consider. questions are generally asked from which subject.Plz help me out.

2006


Define Electrical Insulation and examples of Solid,Liquid and Gaseous insulating materials?

1763


solar inverters was not connected to the nuteral link .this nutwral possible to any other systems

1886


TYPE'S OF BREKAR ,WHAT IS TRANSFORMAR & SAFTY. STARTER DOL & STAR DELTA STARTER.

2592


in general it is observed in power stations, the tertiary winding is used in higher rating Y-Y auto transformer but not in Y-Y power transformer. is the tertiary winding is compulsory then why it is not using in power transformer 

1810


Control wiring of a dol starter for forward and backward

1587