Answer Posted / abdul ghani fatima fertilizer
Dear Friends.
If Generator is running in Island mode then it will be
tripped due to excitation failure so all the load will be
cut off, and if the Generator is running in Parallel even
then it will be tripped on under excitation.
But if the excitation protection fails then it will be
tripped on reverse power.
And if there is no any protection then during parrallel
running the faulty generator shall act as motor, and if
Generator running in Island mode it will be continuous run
without output rated voltage so loads shall not be
continued.
| Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
Hi,I am working in abroad for more than 3 years in a company operating with 11kv and 6.4 MW power. I need c licence in India,can I? some other says only i can get if i work for 2 years in india only! anybody kindly clarify by doubt.Thanks
Load transfer in 11kv double busbar switchgear - operation.
what is there inside an inverter and how it works?
We have given to 3phase supply to ups system & how can coming netural
the grid connection required for a 50 MegaWatt fotovoltaic powerplant is higher or lower than 35kv (high or medium tension)?
how will calculate the safe starting current of 3-phase squirrel cage induction motor?
is it possible to test of bus bar in high rise building without completed full floor ?
What are the electrical engineer roles and responsibilities in chemical plant?
Why does the adjacent zone of protection overlap?
wow to calculate the transformer rating(KVA)
Form S and "c" license application both are same? @ tneb portal
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?
why we r not earthed Control cable of C.T. terminals
which stabilizer is better ? AVR, Servo Stabilizer, Static stabilizer etc & why explain it
Explain the operation of variable frequency transformer?