Dear sir/mam
Iwant complete details of Naintenence of 33kv/433v
Transformer having 1250 KVa

Answer Posted / virendra1981

Dear friend,

In routing maintenance you should take care of the
following .

Daily .

1. Percentage loading of a transfomer
2. Make sure the bucholze realy is full with oil no inert
gas is there if there then purge the same.
3. Check the record the Reading of OT & WT
4. Check manualy for any leakage from any part of the
transformer.
5. Check for any abnormal heating & noice in transformer.


Quarterly.

1. Check & change the silica gel of the breather .
2. Check teh Safety function tripping of HT breaker related
to transformer. ( tripping point of OT , WT & Tranfomer )

Annualy.

1. Check & fillter the Trasformer oil
2. with complete shut down take the reading of insulation
resistance of the transformer winding.
3. Open & check the condition of transformer HT & LT
bushing for any cracks or damage.
4. Chceck the condition of the earthing pit & take the
earthing resistance value for all the earthing pit (
Neutral & Body earth )

Do the same as directed & have a trouble free operation of
the transformer for a long period of time

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to make an earthing certificate

1762


what happen when increase or decrease size of lamp,light.glass.

1488


I have a drawing of a wound rotor induction motor for a crane. This crane motor has 5 forward speeds & 5 reverse speed implemented of course with different amount of resistance for each speed setting selected. What has got me scratching around is the fact that 8 of the 10 speed selections switch in uneven (unbalanced) amounts of resistances on each of the 3 connections to the motor's rotor.Can this be possible? I would have assumed this would produce unbalanced rotor currents and therefore vibration in the motor. I would greatly appreciate anyone's comments on this. Many thanks, Confused.

1403


what is the write prosidure of stringing of 8meter pcc pole.

1976


what will be happen if earth point is being used for as a neutral point for raw power , and same will be used for ups earthing

1613






I don't understand why when we connect high voltage source in DC to electronic motor , we must add capacitor and resistor in parallel ? (I know that we use capacitor because we want to absorb the current that in the first second electronic motor in opposed with current course produce. ) what are the feature of Resistor and in such situation ?

1370


what is cathodic protaction?

1492


WHAT IS LOAD CELL

1697


What are the advantages and disadvantages of open loop control system?

654


A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?

672


What are the basic elements used for modeling mechanical translational system?

608


if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .

1156


what is the meaning of osr in transformer.

1543


how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???

1249


If you have an earth with pilecap then your resistance is really low. why and how?

1436