what current is taken from a double wound 500kva transformer
Answer Posted / bala
hai
DATA
Tr rating = 500 kva
voltage rating = 415 v
Calculation
500 / rt 3 x .415 0r
500 x 1000 / rt 3 x415 = 695 A
i hope now u are clear
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
What is the main use of rotary phase converter ?
I just purchased a 4 position cam switch to be used to operate a 3-speed blower motor. The motor is a 10 amp motor and has 3 wires that are used to control speed. The cam switch was rated at 660V 20 amps but when I received it, I noticed that it has AC-15 operational current rating (Ie) of 4/5 amps. If I am reading the label correctly. the 4/5 amps is related to 440v/220V (Ue). Other ratings are AC-3: 5.5A, AC2: 7.5A and AC-4: 1.5A. My questions are 1) Is it safe to use this switch with the motor I have 2) what is the difference between the 20 amp Ith ratting and the Ie operational ratings?
what are factors to be consider to design a HT & LT motor?
what is the diference between the 4pole & 6pole DC Motors & what is advantage 6pole over the 4pole ?
describe the A.C. Generator Testing procedure
at what rate the micro controller increment its timer....is it 1micro seconds or 1/(12*10^6) seconds
We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?
diameter of cable and core is doubled then the value of capacitance is
hi, could someone help me to find a control design for syncronising panel .
ANY ONE TELL ME ABOUT generator synchronization panel panel to synchronise 3 gen of 250kva both automatic and manual. 2 gen output vol 415 3ph, 1 gen output vol 400 3ph SEND THE DETAILS DIAGRAM ON THIS EMAIL ADDRESS ayazleo@hotmail.com as soon as possilble best ragrds electrical engineer ayaz mahmood SAUDI TECH
Is it advantages of having star-delta vfd than normal star vfd , if yes why?
why we use two slope(differential & restraining) in differential relay.but in busbar protection differential we are using only one slope?please explain
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?
what is the difference between elcb and rccb ?