1.After synchronising the alternator to the grid,how we r
delivering power to the grid?if the i/p increases does the
speed hence frequency increases?
2.y the power factor is changing when exitation changes?what
is the relation with p.f and flux?
Answer Posted / ashwani malhotra
The real power is goverened by Frequency of prime mover.
The relation between real power and frequency of prime
mover is inversly proportional.So as load increase on the
grid it is shared by the genset and increased load met by
reducing the speed .Then governer throat open more to enter
more steam to maintain the frequency.
The voltage at alternator is controlled by the reactive
power flow. So increase in excitation beyond normal provide
capacitive VARs and decrease in excitation less than normal
provides the Inductive VARs required by the system.
generally the system comprises of Inductive load like
motor,transformer so alternator operate mostly in Under
Excitation state.
Is This Answer Correct ? | 1 Yes | 3 No |
Post New Answer View All Answers
What type interview questions ask in Electrical technicians
features of hbc fuses
What is the effect of pi controller on the system performance?
i have a 4 Mva transformer 34.5 kv / 480-277 v and i used 2 parallel 3200 amp bus duct for the secondary feeder using 3 ply of bus bar ( 3/8" x 5" ) as a common where the flexible link terminated and 6300 amps breaker for the main, the lower bus duct reaches 70 degrees and the upper bus duct reaches 55 degrees when i used thermal scanner. why the temperature is not balance when the load reaches 3600 amps.
What is servo motor and what are different types of servo motor
what are the maximum available current, voltage ratings and switching speeds of the power electronic devices thyristor, power mosfet, igbt, and mct?
what types of electrical & mechanical test conducted in switchyard?
How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?
What is the method of estamating of cable, CB,MCB ?
impliment (AB)`+C to transistor representation
what is the transformer rush current?
Why an ac solenoid valve attract the plunger even though we interchanges the terminal? Will the poles changes?
How can calculate the rating of a servo stabilizer for given a specific load
Role of active and reactive Power sharing in between two synchronized Generators, Droop Setting role ?
How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?