when current lags behind voltage how does it affect the
circuit.In other words what is the significance of lagging
current?

Answer Posted / karl

I dont think the significance is that you will lose energy.
For example if I was to connect a capacitor in a AC
circuit, it would charge and then discharge back into the
supply. Therefore not using any real power. This would be
the same for a pure coil with its reactive energy. I think
the problem with a poor PF is that for a certain load you
may need to have a bigger transformer or generator. For
example a 1kW load with PF if 0.5 would need a xformer size
of 2kVA. If the PF was 1 you would need only a 1kVA
xtransofrmer even though you are still using the same power
and therefore energy.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the ratio of Booster transformer?

1639


how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.

1444


What are the three major categories of error?

658


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1676


What will happen if a dc source is given to a tubelight. Will it work or wont it work....

1478






actually i can't understand what is 3dB ? and it's really not clear to me.please any one let it me be cleared.

1718


why we r not earthed Control cable of C.T. terminals

1537


How does an induction motor start?

729


please send 5yearje solved papers on my email himmatsinghnathawat@gmail.com

1465


how a resistor resists to flow the current?how an inductor oppses the sudden change in current?how a capacitor opposes a DC voltage.

2282


I want to make street light with solar system ... What may I do for procedure and how much of estimation for each material ... If any one knows guide me and inform this id : aravindd7@gmail.com

1338


What are the effects of adding a zero to a system?

667


Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.

1547


I have a 380 KVA DG set. How can i find out 1. My Fuel Consumption per hr ? 2. Electricity produced in 1 Hr. ? 3. If load varies then how does it affect fuel consumption & electricity produced ? Please HELP !!! Really need an answer.

2113


Why Neutral Isolation is required?

1814