what is the principal of flow transmeter,level trans
meter,presser transmeter?
Answer Posted / parag
First of all transmitter is a transducer which convert
input parameter value to 4-20 mA signal that can be send to
long distance like Control room DCS, PLC,...
there are different priciples on which different
transmitter works for measuring either level, flow, or
pressure.
We can use pressure transmitter to measure level and flow.
Differential Pressure transmittter works on capacitance
principle.
Differential pressure transmitter can be used to measure
pressure across any tank, vessel, pump to know the pressure
difference between its upstream and downstream.
Same Differential pressure transmitter can be used to
measure flow if we use across upsteam and downstream of
orifice with square root as flow is directly praportional
to square root of pressure difference across the
restriction.
Even we can use differential pressure transmitter to
measure level as Delta pressure is equal to height of the
tank multiplied by density of the fluid inside.
| Is This Answer Correct ? | 11 Yes | 2 No |
Post New Answer View All Answers
How d.p. Transmitter can be applied to open tank?
How can we test a bently nevda 3500/42M accelerometer monitor card by simulating it with test equipment?. what king od of signal (milli volts or volts or or resistance ) we should feed in the terminals of the card?
what is the difference between magnetic flow meter and mass flowmeter
What is the difference between working pressure and calibration pressure of a control valve
what is output of FOUNDATION FIELD BUS transmitter
Identification of ss fittings, pilot valves, relief valve.
what is RTV function in in process control?
I want to measure and control level in tank of size 10*5 filled with gasoline, so plz give me the solution with clear details. how to select transmitter and sensors.
what is the reset offset and control system in instrumentation
hey any one got the papers of SAIL and HPCL plz do help me by posting them to my mail ID's naren07_87@yaho.co.in, surenarendra@gmail.com
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.
Why upper weighing limit of electronics balance is 90% of the total weighing capacity?
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....